BBT Heat-Shrinkable Bus Bar Tubing
       BBT(1kV/10kV)  is a well insulated and track-resistant, heat-shrinkable, polyolefin protective  sleeve for bus bars. It is widely used to protect the rectangular, square and round bus bars found in low or medium voltage switching equipment.
 
       
  
    
      
        
          
            | Specifications | 
            
           
          
            
              
                
                   Item   | 
                   Test Method  | 
                   Specifications  | 
                 
                
                   Shrink  Temperature (°C)   | 
                     | 
                   110  | 
                 
                
                   Operating Temperature Range (°C)   | 
                     | 
                   125  | 
                 
                
                   Tensile Strength (Mpa)   | 
                   ASTM D2671  | 
                   ≥10  | 
                 
                
                   Elongation at break (%)   | 
                   ASTM D2671  | 
                   ≥450  | 
                 
                
                   Aging in Circulating-air Oven   | 
                   ASTM D2671  | 
                   136.0±1.0°C, 168hrs  | 
                 
                
                   After aging   | 
                   Tensile Strength (Mpa)  | 
                   ASTM D2671  | 
                   ≥10  | 
                 
                
                   Elongation at break (%)  | 
                   ASTM D2671  | 
                   ≥400  | 
                 
                
                    Flexibility at -40°C, 4h  | 
                   ASTM D2671  | 
                   No cracking  | 
                 
                
                    Volume Resistance (Ω .cm)  | 
                   ASTM D876  | 
                   ≥1013  | 
                 
                
                    Dielectric Strength(15kV/mm)  | 
                   ASTM D2671  | 
                   ≥15  | 
                 
                
                    Heat shock  | 
                   200°C±3°C, 4h  | 
                   No cracking  | 
                 
                
                    Oxygen index  | 
                   ASTM D2863  | 
                   ≥30  | 
                 
                
                    Water absorption  | 
                   ASTM D570A  | 
                  <0.5%   | 
                 
              
              | 
           
        
        | 
    
  
  
  
  
    
  
  
    
  
  
  
  
  
    | Size for BBT-1kV | 
     | 
     | 
     | 
  
  
    |   | 
     | 
     | 
     | 
     | 
     | 
     | 
  
  
    | Size (inches) | 
    Size (mm) | 
    Inside Dia. (mm) | 
    Wall Thickness  | 
    Inside Dia. (mm) | 
    Wall Thickness  | 
    Cable Range (mm2) | 
  
   
   
  
    | 1-1/4" | 
    30/15 | 
    31.5±1.0 | 
    0.5±0.15 | 
    15 | 
     1±0.15 | 
    30 | 
  
  
    | 1-3/8" | 
     35/16 | 
     37±1.5 | 
    0.5±0.15 | 
     16 | 
     1±0.15 | 
     40 | 
  
  
    | 1-9/16" | 
     40/20 | 
     40.5±1.5 | 
    0.5±0.15  | 
     20 | 
     1±0.15 | 
     40 | 
  
  
    | 2" | 
     50/25 | 
     50.5±2 | 
    0.5±0.15 | 
     25 | 
     1±0.15 | 
     50 | 
  
  
    | 2-3/8" | 
     60/30 | 
     60±3 | 
    0.8±0.2  | 
     30 | 
     1.3±0.2 | 
     60 | 
  
  
    | 2-3/4" | 
     70/32 | 
     70±3 | 
    0.8±0.2 | 
     32 | 
     1.5±0.2 | 
     80 | 
  
  
    | 3" | 
     80/40 | 
     80±3 | 
    0.8±0.3 | 
     40 | 
     1.5±0.3 | 
     80/100 | 
  
  
    | 3-1/2" | 
     90/43 | 
     90±4 | 
    0.8±0.3 | 
     43 | 
     1.5±0.3 | 
     100 | 
  
  
    | 4" | 
     100/50 | 
     100±4 | 
    0.8±0.3 | 
     50 | 
     1.5±0.3 | 
     100/120 | 
  
  
    | 5" | 
     120/60 | 
     120±4 | 
    0.8±0.3  | 
     60 | 
     1.5±0.3 | 
     150 | 
  
  
    | 6" | 
     150/75 | 
     150±4 | 
    0.8±0.3 | 
     75 | 
     1.5±0.3 | 
     180 | 
  
  
    | 7" | 
    180/70 | 
    180±4 | 
    1.0±0.3 | 
    90 | 
     1.8±0.3 | 
    210 | 
  
  
    | 9" | 
    235/105 | 
    235±4 | 
    1.0±0.3 | 
    118 | 
     1.8±0.3 | 
    250 | 
  
  
  
  
  
    | Size for    BBT-10kV | 
     | 
     | 
     | 
     | 
     | 
     | 
  
  
    | Size (inches) | 
    Size (mm) | 
    Inside Dia. (mm) | 
    Wall Thickness  | 
    Inside Dia. (mm) | 
    Wall Thickness  | 
    Cable Range (mm2) | 
  
   
   
  
    | 3/4" | 
    20/9 | 
    20±0.8 | 
    1±0.2 | 
    9 | 
     2.5±0.2 | 
     20 | 
  
  
    | 1-1/4" | 
     30/13 | 
    30±0.8 | 
    1±0.2 | 
     13 | 
     2.5±0.2 | 
     30 | 
  
  
    | 1-1/2" | 
     40/15 | 
    40±1.0 | 
    1.2±0.2 | 
     15 | 
    2.5±0.2 | 
     40 | 
  
  
    | 2" | 
     50/20 | 
    50±2.0 | 
    1.2±0.2 | 
     20 | 
     2.8±0.2 | 
     50 | 
  
  
    | 2-3/8" | 
     60/24 | 
    65±3.0 | 
    1.2±0.2 | 
     24 | 
     2.8±0.2 | 
     60 | 
  
  
    | 3" | 
     80/32 | 
    80±4.0 | 
    1.2±0.3 | 
     32 | 
     2.8±0.2 | 
     80/100 | 
  
  
    | 4" | 
     100/40 | 
    100±4.0 | 
    1.2±0.3 | 
     40 | 
    2.8±0.2 | 
     100/120 | 
  
  
    | 5" | 
     120/48 | 
    120±4.0 | 
    1.2±0.3 | 
     48 | 
    2.8±0.2 | 
     150 | 
  
  
    | 6" | 
    150/60 | 
    150±4.0 | 
    1.2±0.3 | 
     60 | 
     2.8±0.2 | 
     200 | 
  
  
    | 7" | 
    175/75 | 
    175±4.0 | 
    1.5±0.3 | 
    88 | 
     3.2±0.3 | 
    210 | 
  
  
    | 8" | 
    210/85 | 
    210±4.0 | 
    1.5±0.3 | 
    105 | 
     3.2±0.3 | 
    240 |